TECHNICAL DATA SHEET
Built-in LPG detector, with catalytic sensor and relay output.
• Visual and acoustic signalling of any gas leaks
• The output relay can be connected to a normally open 'NO' or normally closed 'NC' solenoid valve and can interrupt the gas flow once a leak is detected.
• On the front there are three indicator LEDs, the green one indicates that the power is on, the yellow one indicates that the gas sensor is faulty, and the red LED indicates that the gas concentration measured in the air is higher than the alarm threshold.
• The detector automatically signals the sensor's expiration date
• Reset/test button for alarm silencing
• The package includes two interchangeable white and anthracite colored front panels.
Orbis Onda LPG Flush-Mounted Gas Detector with 230V Catalytic Sensor
ORBIS 
Built-in LPG detector, with catalytic sensor and relay output.
* Visual and acoustic signalling of any gas leaks
* The output relay can be connected to a normally open 'NO' or normally closed 'NC' solenoid valve and can interrupt the gas flow once a leak is detected.
* On the front there are three indicator LEDs, the green one indicates that the power is on, the yellow one indicates that the gas sensor is faulty, and the red LED indicates that the gas concentration measured in the air is higher than the alarm threshold.
* The detector automatically signals the sensor's expiration date
* Reset/test button for alarm silencing
* Two interchangeable white and anthracite front panels are included in the package
* Adaptable to the main civil series
TECHNICAL CHARACTERISTICS
Power supply: 230 V
* Rated frequency: 50 / 60 Hz
* Contact rating: 5 A / 250 V AC
* Contact type: In exchange
* Current consumption: 20 mA max
* Operating temperature: -10 °C to +40 °C
* Relative humidity: 30% – 90% RH
* Acoustic signal: 85 dB(A) at 1 m.
* Degree of protection: IP 40
* Installation: Wall or on 3-module box (type 503)
* Compatible plates (*): ABB (Chiara series); BTICINO (Axolute, Living, International, Light, Light Tech, Magic, Matix series); VIMAR (Idea, Plana, Eikon series); LEGRAND (Vela Quadra, Vela Tonda, Cross series); GEWISS (Chorus, Playbus series); SIEMENS (Delta Futura, Delta Geo series)
* Electronic self-diagnosis with sensor fault indicator
* Intervention threshold at a concentration of 8% of the LEL (Lower Explosive Limit) of the gas
* Intentional preheating delay after the appliance is connected to the mains, approximately 1 minute
* Intentional delay of acoustic alarm and relay control approximately 15 seconds
* Catalytic sensor life: 5 years from the date the detector is powered on